CoolRow DX 10 kW with EC Fans SideFrontCooler

Delivery Time
2-3 Tage

CoolRow DX 10 kW with EC Fans - version SideFrontCooler/p>

  • 48 U
  • (WxDxH in mm) 300x1200x2200
-
Incl. 19% VAT, excl. Shipping Cost
SKU
ECDX-S-3-12-48-SFR-10

CoolRow DX 10 kW with EC fans - version SideFrontCooler

The CoolRow® is a highly energy-efficient and efficient in-line cooling system for cooling server rooms and data centers in a rack installation based on the cold aisle aisle concept. Powerful fans suck in warm air at the back and blow out cold at the front. The CoolRow® is suitable both for a cold aisle enclosure and a warm aisle enclosure with and without raised floor. Likewise, the Coolrow DX is to operate as a side cooling device for directly cooled server racks, in addition even in a combination of two different air conditioning methods. Here, the process heat is absorbed in a highly efficient manner directly in the back of the rack and cold air is discharged forward into the server room. This adaptive functionality enables a unique indoor climate concept with the efficiency of a directly cooled server rack.

  • Row cooling unit with 10 kW cooling capacity
  • flexible use in cold and hot aisles
  • no double floor necessary
  • pressure control
  • Coolants Coolant DX version
  • flexible and easy to install
  • Stocks can be retrofitted
  • efficient inverter external device
  • (WxDxH in mm) 300x1200x2200

Description and technical data of the side refrigerator:

Technical Datasheet Lehmann CoolRow Air Conditioners
CoolRow 10 kW version
COOLING CAPACITY
Full kW 3-10.2
Sensitive kW 3-9.3
Air inlet temperature 35 ° C
Relative humidity% 35
Power consumption Unit kW 4.4
Current consumption Unit A 6.3
FANS n. 3
Type EC Radial EC Radial
Air flow m³ / h 2500
Ext. Static pressure Pa 20
COMPRESSOR
R410A
Type Hermetic BLDC
Number n. 1
Kältekreisläuf n. 1
Speed ​​RPM 2400
Modulation range RPM 2400-4800
AIR FILTER n. 1
G4
GLOBAL ELECTRICAL DATA (ACCESSORIES INCLUDED)
Voltage V-ph-Hz 400-3-50 + N + T
Power consumption kW 4.4
Total current consumption A 6.3
Max. Current consumption FLA A 4.5
Starting current LRA A 4.5
SOUND PRESSURE LEVEL, 3 m free field clearance (ISO3746) dB (A) 65 from the front
DIMENSIONS
Width 300 mm
Depth mm 1000
Height mm 2000 + 100
Shipping weight kg 135
AIR COOLED LIQUID
Outside air temperature 35 ° C
Number n. 1
Series and size CR 19 Kc
AXIAL FANS n. 1
Amount of air m³ / h 5900
Rated power kW 0.49
Max. Current consumption FLA A 2.36
POWER SUPPLY V-ph-Hz 230/1/50
SOUND PRESSURE LEVEL, 10 m clearance in free field dB (A) 41
DIMENSIONS
Length 840 mm
Width 780 mm
Height mm 800
Transport weight 31 kg
CONNECTION OF REFRIGERANT LINES IN / OUT mm 18/16

More Information
SKU ECDX-S-3-12-48-SFR-10
Product availability delivery time on request
width 300
depth 1200
height 2200
U 48