Current consumption rest (at 24 V) 155 mA - 350 mA * Current consumption Alarm (at 24 V) 255 mA - 535 mA * (plus 250 mA per extinguishing fan)
Monitored inputs / outputs
Door contact
Reset (reset input)
Max. 5 temperature sensors *
Extinguishing fan
Cut-off
Manual release
Data A / B bus connection and 24 V power supply for external modules
Network*
Potential-free relay outputs
Pre-, main alarm per detector *
Disorder
Max. 5 programmable relay
Triggered deletion
Service (Separate)
Contact load alarm / fault relay 1 A / 30 V DC
Integrated extinguishing agent container Extinguishing Bowl capacity Max. 2 x 2 liters Extinguishing agent Novec ™ 1230 from 3M ™ or on request: FM-200 (HFC-227ea) Property shutdown integrated relay control Weight (maximum configuration) 32 kg * Dimensions (H x W x D mm) 88.1 x 483 x 670 Minimum required installation depth 900 mm
* Depending on the configuration level, extract from the technical manual TITANUS RACK · SENS®