TITANUS RACK · SENS® 88.9 mm height (2U) Maximum configuration
Technical specifications:
Current consumption rest (at 24 V) 155 mA - 350 mA *
Current consumption Alarm (at 24 V) 255 mA - 535 mA * (plus 250 mA per extinguishing fan)
Monitored inputs / outputs
Door contact
Potential-free relay outputs
Contact load alarm / fault relay 1 A / 30 V DC
Integrated extinguishing agent container
Extinguishing Bowl capacity Max. 2 x 2 liters
Extinguishing agent Novec ™ 1230 from 3M ™ or on request: FM-200 (HFC-227ea)
Property shutdown integrated relay control
Weight (maximum configuration) 32 kg *
Dimensions (H x W x D mm) 88.1 x 483 x 670
Minimum required installation depth 900 mm
* Depending on the configuration level, extract from the technical manual TITANUS RACK · SENS®
3M and Novec are trademarks of 3M Company
SKU | TITANUS RACK·SENS 2HE Maximalausbau |
---|---|
U | 2 |
width | 483 |
depth | 670 |